Solenoid valves are control units which, when electrically energized or de-energized, either shut off or allow fluid flow. The actuator takes the form of an electromagnet. When energized, a magnetic field builds up which pulls a plunger or pivoted armature against the action of a spring.
A typical pneumatic solenoid valve of that era may have consumed 6 Watts of power and lasted 10 million cycles. Today a pneumatic valve can be operated with power consumption as low as 0.1 Watt with a life of over 200 million cycles. This is an amazing 60 times less energy with 20 times the life.
A solenoid is a device comprised of a coil of wire, the housing and a moveable plunger (armature). When an electrical current is introduced, a magnetic field forms around the coil which draws the plunger in. More simply, a solenoid converts electrical energy into mechanical work.
A continuous duty solenoid works much like a regular starter solenoid, opening and closing a circuit in order to turn the power flow off and on. As you might have guessed, however, in the case of a continuous duty solenoid the power flow is more of a constant, whereas a starter solenoid operates intermittently.
A solenoid is connected to a battery so that a steady current flow through it.
They do not require external pressure or a supplementary actuator to operate. Direct-acting solenoid valves can open or close even when there is no pressure difference across valves. The plunger will move in response to the electromagnetic field created by energizing the solenoid.
A 12 volt DC coil opens and closes the valve in less than one second. It is rated for continuous service and draws 2.50 amps, for a nominal power consumption of 40 watts.
Solenoid Valve Wiring
Take one wire from each solenoid, twist together and connect to the common (usually white) wire of your multi-conductor irrigation cable. Connect each of the other individual wires to a different colored wire. Record zones against wire color for later reference.
The valve opens by direct action when electromagnetic activity in the coil pulls the plunger up to allow the media to pass through (or vice versa for usually open valves).
Solenoid valves eliminate the need for manual or pneumatic control of a pneumatic circuit and only require an electrical input (and air pressure for piloted valves) to operate, this makes them easy to program and install in a wide variety of applications.
Starters Can Fail Due To Low Battery voltage
Typically what happens is the excess current created as a result of the low voltage causes the contact within the solenoid to weld together or even burn through.
a solenoid doesn't need any voltage at all, it's good existing just as it is.
While the majority of solenoids are designed to pull, a simple design change can allow them to push. The only modification necessary is to extend the internal end of the plunger with a pushrod.
When a solenoid is first energized, its coil receives a pulse of high inrush current that decreases as the plunger closes. If the plunger does not close, the high inrush current continues, which can cause the coil to overheat and burn out. This is the most common cause of solenoid failure and spotting it is easy.
Rusting, power failure, irregular pressure, missing equipment, an incorrect amount of voltage or current, dirt stuck in the system and corrosion are some of the possible reasons why a solenoid valve may not properly close or open.
Other issues that present a bad solenoid
A blown fuse in the starter circuit could be the cause of a no-start problem. Broken or corroded wiring – Damaged or dirty wires to the battery or to the starter solenoid (or wires that are loose) can prevent sufficient power from reaching the starter.
If there's no problem with the solenoid, you could be looking at these problems instead: A dead starter battery that delivers no power to the solenoid. A corroded battery terminal or loose battery cable that reduces battery voltage to the solenoid. Loose wiring or cables can create a bad electrical connection.
If there's no power to the coil or if power is interrupted, the solenoid will cease functioning and remain in whatever position it was last in. Often, power interrupts to the circuitry can cause the valve to stick, and it will remain that way even after you restore power, requiring a reset.
Solenoid coil failure can be caused by a number of factors. Applying an incorrect voltage to the coil will cause it to fail and may cause the coil to burn out. Electrical surges or spikes may also damage the coil. Burnt out coils cannot be repaired and will need to be replaced.
Interpreting the directions on a solenoid can be tricky. After all, there are usually two sets of wires: the power wires and the load wires. The power wires supply electricity to the solenoid, while the load wires connect to the device that the solenoid is controlling.
Does a solenoid have positive and negative? The magnetic field in a solenoid has a north pole, but the polarity of a solenoid valve does not matter. That's because the polarity induced in the core of the solenoid reverses if the current in the coil reverses, so the motion of the core is the same either way.